Zhejiang Hangpu Electric Appliance Co., Ltd.
Products
Contact Us
  • Contact Person : Mr. Tang Tom
  • Company Name : Zhejiang Hangpu Electric Appliance Co., Ltd.
  • Tel : 86-0577-27871266
  • Fax : 86-0577-27871263
  • Address : Zhejiang,yueqing,No.55 Changcheng road, LiuShi ,YueQing city,ZhengJiang,China
  • Country/Region : China
  • Zip : 325604

Circuit breaker PDM1-630 4P White Cover

Circuit breaker PDM1-630 4P White Cover
Product Detailed
Related Categories:Circuit Breakers

Detailed Product Description


Moulded Case Circuit Breaker PDM1(CM1) series is one of our new type products developed and manufactured adopting international advanced technology. It is supplied with rated insulation voltage 800V (PDM1-63 is 500v),  AC50Hz , rated operating voltage 690V or below(PDM1-63 is 400v). The MCCB used for not frequently turn-on or trrn-off and starting of motor in the circuit which rated operating current lower than 800A. Also can keep the line circuit and power supply from damage when the motor overload, short circuit or under-voltage.

 

The MCCB PDM1 has 3 models distinguished by ultimate short circuit breaking capacity: Typical type(L), Second high breaking type(M), High breaking type(H). The characteristics of MCCB PDM1 are samll size, performance upgrade, arc-over distance short(some models have no arc-over distance), vibration resistance, etc. They are the right product for family and ship use.

The products conforms to the standards below:

IEC 60947-1 & GB 14048.2 General.

IEC 60947-2 and GB14048.2 Low voltage breaker.

IEC 60947-4 and GB 14048.4 Electromechanical Contactors and motor starters.

IEC 60947-5.1 and B 14048.5 Control circuit electric apparatus of electromechanical.

 

Connecting:

The MCCB can be installed in vertical or horizontal.

The MCCB should go throuth power supplier from 1,3,5, but 2,4,6.

Altitude: blow 2000m.

Ambient material temperature: upon -5centigrade and below 40centigrade (ship use series are 45centigrade )

Inclilation: ±22.5°.

Vibration resistance under the conditions of normal ship vibration, below level 4 of earthquake

In the no explosion danger material which can not corrod metal and destroy insulates.

Keep away from rain and snow.

 

Main technical specifications:

Type

Number of poles

Rated current(A)

Rated operating voltage(V)

Rated insultating voltage(V)

Ultimate short circuit breaking

capacity 400V(KA)

Servies circuit breaking capacity 400V(KA)

PDM1-63L

3P

(6)10,16,20,25,

32,40,50,63

AC400

AC500

25

18

PDM1-63M

39/4P

50

35

PDM1-100L

3P

(10),16,20,25,

32,40,50,63,80,

100

 

AC690

 

AC800

35

22

PDM1-100M

39/4P

50

35

PDM1-100H

3P/4P

85

50

PDM1-225L

3P

100,125,140,

160,180,200,

225

 

AC690

 

AC800

35

22

PDM1-225M

39/4P

50

35

PDM1-225H

3P/4P

80

50

PDM1-400L

3P/4P

 

225,250,315,350,400

 

AC690

 

AC800

50

35

PDM1-400M

3P

65

42

PDM1-400H

3P

100

65

PDM1-630L

3P/4P

 

400,500,630

 

AC690

 

AC800

50

35

PDM1-630M

3P

50

35

PDM1-630H

3P

50

35

PDM1-800M

3P/4P

630,700,800

AC690

AC800

75

50

PDM1-800H

3P/4P

100

65

PDM1-1250M

3P/4P

800,900,1000,1250

AC690

AC800

65

32.5

PDM1-1250H

3P/4P

65

32.5

PDM1-1600M

3P/4P

1400,1500,1600

AC690

AC800

65

32.5

PDM1-1600H

3P/4P

65

32.5

Terms:

The express shipping usually takes 3-7working days dependent on the country delivered to. We are not responsible for any accidents, delays or other issues that are the responsibility of the shipping service.Any import charges or fees are the buyers responsibility.

Please contact us before leaving any negative or neutral feedback. We will work with you to solve the problem.

Thanks for your attention!



Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.